How Long Will My UPS Last? Working Out UPS Runtime and Size

A UPS (uninterruptible power supply) is the battery box that sits under the server or in the comms cabinet. When the power drops, it keeps everything running long enough to ride out a short blip, or to shut things down cleanly in a longer outage.

The question we get asked most is “how long will it last?” The honest answer is that it depends on two numbers: how much power your equipment draws, and how much energy the batteries hold. Once you know those, the maths is simple. This article walks through it, using the same formulas as our free UPS Load & Runtime Calculator.

What a UPS is actually for

Before getting into numbers, it’s worth being clear about the job. A small business UPS usually isn’t meant to keep the office running for hours. It’s there to:

  • ride through short drops and flickers so a two-second outage doesn’t reboot the server or corrupt a database
  • smooth out brownouts and surges that shorten the life of equipment
  • give you time for a clean shutdown when the outage is longer, so servers and storage power off properly and come back up without damage.

For most businesses, the target is enough runtime to cover the common short outage, plus enough margin for an automated, graceful shutdown. If you need the business to keep trading through long outages, that’s a generator conversation, not a bigger battery.

Step 1: Add up the load

Start by listing everything that will be plugged into the UPS and how many watts each one draws. The nameplate on the power supply gives a maximum. Measured draw is better if you have it, because most equipment uses less than its maximum most of the time.

Typical figures for common equipment:

Device Typical draw
2U rack server 500 W
Tower server 350 W
24-port PoE switch (including PoE budget) 250 W
24-port switch (no PoE) 30 W
Firewall or router 40 W
4-bay NAS 50 W
NVR (security recorder) 60 W
VoIP desk phone 8 W

These are rough guides. Real draw varies a lot with the model and how hard it’s working. PoE switches are the one people underestimate: the switch itself might use 30 W, but it’s also powering every phone, camera and Wi-Fi access point plugged into it.

Add them together and you have your load in watts.

Step 2: Convert watts to VA

UPS units are often sold by their VA (volt-amp) rating, with a separate watt rating in the specifications. Watts are the real power your equipment consumes. VA is “apparent power”, which is a little higher because of how power supplies draw current.

To convert, divide watts by the power factor. Modern IT equipment typically has a power factor around 0.9, so:

VA = watts ÷ 0.9

Always check both ratings on a UPS. A unit sold as “1500 VA” might only be rated for 900 or 1000 watts, and it’s the watt rating your load has to fit inside.

Step 3: Add headroom

You don’t want a UPS running flat out. Equipment draws a surge when it starts up, running near the limit makes the UPS work harder and hotter, and you’ll probably add another device next year.

The common rule is to keep the load at no more than about 80% of the UPS rating. That works out to sizing the UPS at 25% above your load:

Recommended UPS watts = load × 1.25

Our calculator flags a load above 70% of an existing UPS’s rating as getting tight, and above 80% as undersized.

Step 4: Work out the runtime

Battery capacity is measured in watt-hours (Wh). If your UPS lists its batteries as volts and amp-hours, multiply them out:

Battery Wh = volts × amp-hours × number of batteries

You can’t use every last watt-hour. The inverter loses some energy turning battery power back into mains power, and draining a battery completely is bad for it. A conservative allowance is to treat about 80% of the battery as usable. That gives:

Runtime (minutes) = (battery Wh × 0.8) ÷ load watts × 60

You can also run it backwards to find the battery you need for a target runtime:

Battery Wh needed = load watts × target minutes ÷ 60 ÷ 0.8

Two worked examples

A small office comms cabinet

A router, a 24-port switch (no PoE), a 4-bay NAS and two VoIP phones:

  • Load: 40 + 30 + 50 + 16 = 136 W
  • VA: 136 ÷ 0.9 = about 152 VA
  • Recommended UPS: 136 × 1.25 = 170 W (about 189 VA)
  • With a single 12 V 7 Ah battery: 12 × 7 = 84 Wh, so (84 × 0.8) ÷ 136 × 60 = about 30 minutes

That’s plenty to ride out a typical short outage and shut the NAS down cleanly.

A small server rack

A 2U server, a 24-port PoE switch, a firewall and a NAS:

  • Load: 500 + 250 + 40 + 50 = 840 W
  • VA: 840 ÷ 0.9 = about 934 VA
  • Recommended UPS: 840 × 1.25 = 1,050 W (about 1,167 VA)
  • With four 12 V 9 Ah batteries: 12 × 9 × 4 = 432 Wh, so (432 × 0.8) ÷ 840 × 60 = about 25 minutes

If you only need 15 minutes for a clean shutdown, you’d need 840 × 15 ÷ 60 ÷ 0.8 = about 263 Wh of battery.

Why real runtime is usually shorter

The formula above is a straight-line estimate. In practice, a few things cut into it:

  • Battery age. UPS batteries lose capacity as they age, even when they’re rarely used. A battery that gave you 30 minutes when new might give you a lot less a few years later. Most manufacturers recommend replacing them on a regular cycle.
  • Heat. Batteries in a hot comms cupboard wear out faster than batteries in a cool room.
  • High loads. Batteries deliver less total energy when they’re drained quickly, so runtime at heavy load drops off faster than the simple maths suggests.
  • The load creeps up. New switches, cameras and access points get added, and nobody re-checks the UPS.

Always cross-check with the manufacturer’s runtime chart for your exact model, and treat the calculator as a planning estimate.

Don’t forget the shutdown

A UPS that keeps the server running for 25 minutes is only half the job. If nobody is in the office when the power goes out at 2am, the battery runs flat and the server crashes anyway.

The fix is automated shutdown: a network management card or USB connection from the UPS to your servers, with software that tells them to shut down cleanly when the battery gets low. It should be tested, because it’s easy to set up and then never check again.

How Peritus Digital can help

We size, supply and install UPS systems for server rooms, comms cabinets and critical workstations across Newcastle and the Hunter. As part of managed IT, we can bring your UPS into the same 24/7 monitoring as the rest of your infrastructure, set up and test automated shutdown, and keep track of when batteries are due for replacement.

If you want to see what an outage would cost you while the systems are down, try our Cost of Downtime Calculator or read what an hour of downtime really costs.

Run your own numbers in the free UPS Load & Runtime Calculator, then get in touch if you’d like us to check your setup.

Let's talk

Talk to Peritus about your IT and cyber security.

Newcastle's local technology partner — practical, plain-English advice and hands-on support for Hunter Region businesses.